EGE-Elektronik Spezial-Sensoren GmbH • http://www.ege-elektronik.com
E11011 1.03
Function
The function of the flow controller is based on the thermo-
dynamic principle.
The sensor is heated internally a few degrees °C compared
to the medium into which it projects. When the medium
flows, the heat generated in the sensor is conducted away
by the medium, i. e. the sensor cools down. The tempera-
ture within the sensor is measured and compared to the
temperature of the medium. The state of flow can be derived
for each medium by the temperature difference attained.
Function of thermodynamic flow controllers
On the basis of this functional principle EGE manufactures
flow monitors for liquid and gaseous media.
Areas of application for flow monitors
Thermodynamic flow monitors function without any mov-
ing parts, therefore they are not subject to failure due to
corroded bearings, torn impellers or deflector deformation.
This reliability is highly valued in many industries. Today,
flow monitors are used both in liquids and in air, and are
employed even in explosive environments.
Monitoring of cooling
The cooling water on welding machinery is monitored
using compact stainless steel devices. This ensures suf-
ficient cooling even for rapid cycles, otherwise the weld-
ing robot will be switched off.
– The cooling lubricant flow is monitored continuously in
processing centres. The tools are protected and have a
greater service life.
In metal processing, e.g. rolling mills and wire drawing
machines, the rolls and coils will be cooled continually.
This is monitored by thermodynamic sensors. Due to the
rough environmental conditions the sensors are designed
for up to 160 °C and settings are made away from the
heat with special amplifiers.
Monitoring of flow medium
– The run-dry protection of pumps is a frequent applica-
tion, which often uses compact sensors with time delay.
In dosing technology the aggregate, usually small flow
quantities, is measured exactly by means of inline sen-
sors. These sensors are inserted like a pipe into the line.
Monitoring of filters and sieves can be ensured by medi-
um flow control; if the flow is progressively reduced, the
filter must be renewed. Where this is not carried out, the
pump is switched off in a second stage should the medi-
um flow drop further. This uses a sensor with two
switching points.
Run-dry protection of a feed pump
Sensors for explosive hazard environments
– The monitoring of cleaning processes using aggressive
media at times is often only possible with special materi-
als, e.g. hastelloy or tantalum.
– Extraction systems for hazardous vapours at laboratory
workstations as well as the hall ventilation in the hexane
processing industry are monitored using airflow sensors.
CIP/SIP processes can be monitored and documented
with flow monitors.